Installation Instructions
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF LossofAC.Stand-bybatterysupplyingpower.
OFF ON No DC output. Short circuit or thermal overload condition or defective unit.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend Function/Description
AC/AC
Low voltage AC input (see voltage output/transformer selection table).
For12VDCoutputuse16VACwith56VApowerratingorhigher.
For24VDCoutputuse28VACwith85VApowerratingorhigher.
---DC+ 12VDC-24VDC@2.5ampcontinuousoutput.
---BAT+ Stand-bybatteryconnections.Maximumchargerate500mA.
ACFAIL
NC,C,NO
(LPS3R only)
IndicateslossofAC(e.g.connecttoaudibledeviceoralarmpanel).
Relay normally energized when AC power is present.
Contactrating1amp@120VAC/28VDC.