Installation Guide

- 6 - LINQ8ACM(CB)
LED Diagnostics:
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) de-energized. Output relay(s) energized.
FACP FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Green Output 1-8 12VDC
Red Output 1-8 24VDC
AC AC Fail AC Normal
BAT Battery Fail Battery Normal
Input/Output Voltage Ratings:
Input Voltage and Source Output Voltage Rating
5VDC (from VR6 regulator) 5VDC
12V (from VR6 regulator) 12VDC
12VDC (from external power supply) 11.7-12VDC
24VDC (from external power supply) 23.7-24VDC
Maximum Output of Altronix Power Supplies:
UL Listed or Recognized Power Supply Output Voltage Setting Max. Output Current
eFlow4NB
12VDC or 24VDC 4A
eFlow6NB
12VDC or 24VDC 6A
eFlow102NB
12VDC 10A
eFlow104NB
24VDC 10A
VR6
5VDC or 12VDC 6A
Tango1B
12VDC and 24VDC
12VDC @ 5.4A and/or
24VDC @ 2.7A.
65W total.