Spec Sheet
LINQ8ACM and LINQ8ACMCB
Network Access Power Controllers
Rev. LINQ8ACM - 10222019
™
Description
Altronix LINQ8ACM and LINQ8ACMCB are dual input network access power controllers which can be 
installed in Altronix wall and rack mount enclosures to facilitate access control deployment. Access 
Power Controller’s dual input design allows power to be steered from one (1) or two (2) independent low 
voltage 12 or 24 VDC Altronix power supplies to eight (8) independently controlled fuse (LINQ8ACM) or 
PTC (LINQ8ACMCB) protected outputs. Outputs are activated by an open collector sink, normally open 
(NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, 
Keypad, Push Button, PIR, etc. LINQ8ACM(CB) will route power to a variety of access control hardware 
devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both 
Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, 
or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually 
selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power 
to multiple LINQ8ACM(CB) modules. This feature allows you to distribute the power over more outputs 
for larger systems. Built-in LINQ
TM
 Network Power Management facilitates monitoring, reporting and 
control of power/diagnostics.
LINQ8ACM and LINQ8ACMCB have built-in LINQ technology which facilitates monitoring, reporting, 
and control of one (1) or two (2) low voltage AC or supervised DC power supply/chargers over the 
network. They report diagnostics via Email and Windows Dashboard Alert notifications, greatly 
reducing system downtime and eliminating unnecessary service calls. LINQ8ACM and LINQ8ACMCB 
retrofit with most currently installed multi-output power supply/chargers.
4.9"(124.5mm)
2.4" 
(61mm)
6.7" (170.2mm)
3.7" 
(94mm)
8’ (203.2mm)
4.5" 
(114.3mm)
Board Dimensions (L x W x H) and Drawing
8” x 4.5” x 1.25” (203.2mm x 114.3mm x 31.8mm)
Mounting Holes’ Tolerance: +/- 0.04 in. (1mm).
LINQ8ACM