TM NAC Power Extender Installation Guide FireSwitch108 - 10 amp NAC Power Extender Rev. 090414 More than just power.
Overview: The Altronix FireSwitch108 is a cost effective managed NAC Power Extender. It interfaces with 12 or 24VDC Fire Alarm Control Panels (FACP) to provide Notification Appliance Circuit expansion support, for additional horns/strobes to allow ADA compliancy. It also provides auxiliary power to support system accessories. It delivers electronically regulated and filtered 24VDC power to Class B or Class A NAC loop circuits.
Power Supply Specifications: AC Input Output Battery Stand-by/Alarm Current Consumption EOL Resistor (end of line) Ground fault maximum test impedance Maximum Loop impedance 120VAC 60Hz, 4.8 amp. Eight (8) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. 10 amp max. total alarm current (configurable as Special Application Aux. ouputs). 7 amp max. stand-by without battery backup. 1 amp max with battery backup including Aux. output. One (1) regulated aux.
Fig. 2 Keep 1/4" spacing from Power-Limited wiring and Non Power-Limited wiring L N 5A 250V AC LOCAL BAT FAIL NC C NO NC C NO AC FAIL unswitched 120VAC 60 Hz Non Power-Limited Battery and AC Supervision Circuit (power-limited). Use separate knockout. AC + BAT – Non PowerLimited DC AC DELAY Door NO 6. 7. C 5. NC 4. enclosure UL Listed for appropriate application. Separate battery enclosure is required to have 50 cubic inches of additional open space.
8. 9. 10. 11. For Class B outputs connect EOL (AL-EOL10) to the last device in each NAC Loop. For applications in Canada use EOL10K-C end of line resistors (to be ordered separately) Form the leads to fit the terminals. Bend radius can not exceed 1/8 in. Do not bend closer than 1/4 in. to the body of the resistor. Connect desired 24VDC devices to regulated Aux. power output terminals marked [+ AUX --- ] (Fig. 2, pg. 4). Output is Power-Limited. 0.25” spacing from Non Power-Limited wiring must be provided.
Power Supply Board Terminal Identification Table: Terminal Legend Function/Description Connect 120VAC to these terminals: L to Hot, N to Neutral. L, G, N Earth Ground should be connected via grounding lug. + DC – 24VDC non-power limited output. Form “C” dry contacts indicate the loss of AC, with AC present terminals marked [NO and C] AC FAIL (delayed) are open, [NC and C] are closed. When loss of AC occurs terminals marked [NO and C] are closed, NO, C, NC [NC and C] are open.
Wiring Diagram: Regulated Supervised NAC Outputs Power-Limited Fig. 4 AC and Battery Supervision Power-Limited AC Input Non Power-Limited 120VAC, 60Hz 4.8 amp Ethernet Connection Common Trouble Sync Power-Limited Regulated NAC Outputs Power-Limited ALL POWER LIMITED WIRING IS TO BE ROUTED UNDER THE CHASSIS (BETWEEN CHASSIS AND BACKBOX) FireSwitch108 Aux. Output Regulated 24VDC @ 1 amp Power-Limited (0.
Connection Diagram: Fig. 5 UP Ethernet LEFT ETHERNET DOWN PRESS DOWN FOR ENTER INP2 Factory Installed Board Interface Cable to Power Supply RIGHT INP1 Fire Alarm Control Panel (FACP) INP2 NO NEGATIVE C EARTH INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 Power-Limited Addressable control module trigger output 24VDC Regulated Power-Limited Output Special Application Output selected as Aux.
Protocol Selection: LCD Function Legend Triggered From 1a 2a 3a 1b 2b 3b 1c 2c 3c 1d 2d Input 1 Input 2 Redundant - Input 1 and Input 2. Input 1 Input 2 Redundant - Input 1 and Input 2. Input 1 Input 2 First Input to go in alarm mode. Input 1 (both horns and strobes). Input 2 (both horns and strobes). 3d 1e 2e 3e 1f 2f 3f 1g 2g 3g 1h 2h 3h Steady Code 3 Follower Mode Amseco/ Potter Carbon Monoxide (CO) Reserved Gentex® Gentex is a registered trademark of Gentex Corporation.
Trouble Memory LCD Indication: LCD Legend A B C N O S G ? Trouble Condition AC trouble. Battery trouble. Common trouble. Normal operating condition. Loop open or open circuit. Loop Shorted. Loop Ground fault. Loop wiring is incorrect. b. Use [Down] to reset all stored troubles. Step 4. AC and Battery Trouble reporting and Sounder Alert Options a.
Battery Calculation Worksheet: Number of Current per Device Devices This column x This column = Equals Device For each device use this formula: FireSwitch (Current draw from battery) A 1 180mA Alarm: 200mA 180mA 200mA FireSwitch Current Auxiliary Devices B Stand-by: Stand-by Alarm Current Current Current per number of devices. Refer to device manual for current ratings.
FireSwitch Applications: 1. General Information: Altronix FireSwitch units are very versatile devices. They can be used with or without specific synchronization modules provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a external synchronization module. Please note that only notification appliances with synchronization capabilities can be synchronized. Contact signal manufacturer for more detailed information.
POSITIVE Horn settings for CO alarm: Gentex, Potter - Horns must be set to Steady mode. System Sensor - Horns must be set for a coded output. NEGATIVE Fig. 9 4. Non-synchronizable NAC Appliances: INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4 When using NAC appliances not designed to support synchronization From FACP NAC 1 feature, it is recommended to use separate output circuits for audible notification appliances (horns) and visual notification appliances (strobes).
6. Synchronizing NAC Power Extender Using Built-in Sync Protocol: FireSwitch units include built-in protocols to support Amseco/Potter, Gentex®, System Sensor® or CooperWheelock® two-wire synchronizable devices, therefore an external sync module is not required (Output Programming Selection Table, pg. 6). In these modes, Input 1 is always used to activate visual notification appliances (strobes), and Input 2 is used to activate and silence audible notification appliances (strobes) (Table, pg. 6).
Fig. 12 NO FireSwitch Logic Board: Programmed for desired Notification Appliance RET1 OUT C EARTH INP1 RETURN NC NEGATIVE NC GND Supervision POSITIVE + SYNC --- Addressable Module FACP (Fire Alarm Control Panel) Class A signaling circuit connection non-silencable configuration.
8. Using a Single FACP Output: When only one FACP output is available, you may connect both Input1 and Input2 to it. Wire [RET1+ and RET1-] to [INP2+ and INP2-]. Both visual and audible notification appliances will be activated simultaneously (Fig. 13, pg. 16). FireSwitch Logic Board Fig.
Appendix A - UL/cUL Listed Compatible Devices for Synchronization A-1 Strobes, Horns and Horn/Strobes Table A-1 below lists Strobes, Horns and Horn/Strobes compatible with FireSwitch NAC outputs.
Appendix A - UL/cUL Listed Compatible Devices for Synchronization (cont’d) A-1 Strobes, Horns and Horn/Strobes Table A-1 below lists Strobes, Horns and Horn/Strobes compatible with FireSwitch NAC outputs.
Appendix A - UL/cUL Listed Compatible Devices for Synchronization (cont’d) A-1 Strobes, Horns and Horn/Strobes Table A-1 below lists Strobes, Horns and Horn/Strobes compatible with FireSwitch NAC outputs.
Enclosure Dimensions (H x W x D) (approximate): 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.94mm) 1.25” (31.