Installation Instructions User Manual

- 2 - eFlow3N Series
Overview:
The eFlow3N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output
(see Power Supply Configuration Reference Chart and Specifications).
eFlow3N Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Nominal DC Outputs
Maximum Supply
Current for Main and
Aux. Outputs (amp)
Power-Limited Output
Input Rating:
120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
PTC Output Ratings
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
[DC] [AUX]
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
eFlow3N
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 N/A 1
3
eFlow3NX
3
eFlow3N4
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 PD4UL 4
2A
3
eFlow3NX4 2A
3
eFlow3N4D
9.78-
13.2
20.0-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 PD4ULCB 4
2A
3
eFlow3NX4D 2A
3
These units are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable to power: sensors,
electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/NFPA70/NFPA72 and the Canadian
Electrical Code, Part 1.
Agency Listings:
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
California State Fire Marshal
(eFlow3N and eFlow3NX)
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH 0.4 amp/2 amp N/A 1.5 Hours/2 amp
12AH 1 amp/2 amp 0.3 amp/2 amp 3.5 Hours/2 amp
40AH (for eFlow3NX refer to Fig. 7, pg. 10) 2 amp/2 amp 1.2 amp/2 amp Over 4 Hours/2 amp
65AH (for eFlow3NX refer to Fig. 7, pg. 10) 2 amp/2 amp 1.5 amp/2 amp Over 4 Hours/2 amp