Installation Guide
eFlow3N Series - 9 -
Door
Wire Strap
(from
Enclosure
to Door)
Battery & AC Supervision
Circuit (power-limited)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using the 40AH or 65AH batteries.
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +
TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
120VAC power mains
(non power-limited)
Class 1
Power-limited
Green
Lead
(ground)
Battery connections
(non power-limited)
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
PD4UL/PD4ULCB
DC Output to devices
(refer to Fig. 3a or 3b
for board configuration pg. 6)
OFF --- 24V
ON --- 12V
ON
ON
1
Switch On - 12V
Switch Off - 24V
Switch Detail
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)
Fig. 6 - eFlow3NX configuration