Installation Guide

- 2 - eFlow3N Series
Overview:
The eFlow3N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output
(see Power Supply Configuration Reference Chart and Specifications).
eFlow3N Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Nominal DC Outputs
Maximum Supply
Current for Main and
Aux. Outputs (amp)
Power-Limited Output
Input Rating:
120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
Class 2 power-limited
PTC Output Ratings
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
[DC] [AUX]
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
eFlow3N
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 N/A 1
3
eFlow3NX
3
eFlow3N4
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 PD4UL 4
2A
3
eFlow3NX4 2A
3
eFlow3N4D
9.78-
13.2
20.0-
26.39
10.15-
13.2
20.2-
26.39
2A
3
3.5A 5A/250V 3A/32V 960 PD4ULCB 4
2A
3
eFlow3NX4D 2A
3
These units are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable to power: sensors,
electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/NFPA70/NFPA72 and the Canadian
Electrical Code, Part 1.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
California State Fire Marshal
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH 0.4 amp/2 amp N/A 1.5 Hours/2 amp
12AH 1 amp/2 amp 0.3 amp/2 amp 3.5 Hours/2 amp
40AH (for eFlow3NX refer to Fig. 7, pg. 10) 2 amp/2 amp 1.2 amp/2 amp Over 4 Hours/2 amp
65AH (for eFlow3NX refer to Fig. 7, pg. 10) 2 amp/2 amp 1.5 amp/2 amp Over 4 Hours/2 amp
Altronix Corp.
140 58th St. Brooklyn, NY