Installation Instructions
eFlow102NV Series Installation Guide - 7 -
Battery
Connection
Battery & AC
Supervision Circuit
J1
AC Delay
NC C NO NC
C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOL NO GND
SUPERVISED RESET
+AUX-
- BAT +- DC +
L G N
PD8/PD8CB
PD16W/
PD16WCB
220VAC
power mains
DC Output to Devices*
(refer to Fig. 3a, 3b, 4a, 4b
for board configuration, pg. 6)
Ground
Lug
Optional Rechargeable
Stand-by Battery
CAUTION: Power supply board is factory set for 12VDC. Use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Fig. 5 - eFlow102NV Configuration
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
* Outputs are non power-limited:
eFlow102NV, eFlow102N8V, eFlow102N16V.
Outputs are power-limited:
eFlow102N8DV, eFlow102N16DV.