Installation Instructions

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend Function/Description
AC/AC
Low voltage AC input (Voltage Output/Transformer Selection Table).
For 6VDC output use 16VAC or higher with 24VA power rating or higher.
For 12VDC output use 16VAC or higher with 40VA power rating or higher.
For 24VDC output use 28VAC with 175VA power rating or higher.
Caution: Do not apply voltages above 28VAC (28VAC is maximum input rating)
- DC + 6VDC-12VDC-24VDC @ 4A continuous power limited output.
+ BAT - Stand-by battery connections. Maximum charge rate 300mA.
ALTRONIX CORP.
BKLYN, NY 11220
+ DC -- + BAT -- AC AC
AC
DC
MADE IN U.S.A.
6 V 12 V 24 V
SW1 ON OFF OFF
SW2 OFF
OFF ON
SW1
SW2
1 2
ON
DPS5 - Board Drawing: ST3 Drawing:
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.
IIDPS5 - Rev. 092501 E06P