Installation Instructions
DPS1
Power Supply/Charger
Overview:
DPS1 power supply/charger converts low voltage AC input into 6VDC or 12VDC @ 1.2A or 24VDC @ 750mA of con-
tinuous supply current (see specifications). This general purpose power supply has a wide range of applications for access
control, security, and CCTV system accessories that require additional power.
Specifications:
Voltage Output/Transformer Selection Table:
Output Voltage Selector (JMPR) Transformer
12VDC @ 1.2A continuous supply current
Leave J1
and J2 Intact
16.5VAC / 20 VA
(Altronix model TP1620)
24VDC @ 750mA continuous supply current
Cut
Jumper J1 Only
24VAC / 40 VA
(Altronix model TP2440)
6VDC @ 1.2A continuous supply current
Cut
Jumper J2 Only
12VAC / 20 VA
(Altronix model TP1220)
Installation Instructions:
1. Mount DPS1 in the desired location/enclosure.
2. Unit is factory set for 12VDC. For 6VDC output cut jumper J2, for 24VDC output cut Jumper J1.
3. Connect proper transformer to terminals marked [AC] (refer to Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery, DC output).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Devices to be powered should be connected to terminals marked [+ DC] and [DC - BAT],
carefully observing polarity.
6. Connect battery to terminals marked [BAT +] and [DC - NEG] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used, a loss of AC will result in a loss of output voltage.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Input:
• 6VDC or 12VDC output - use TP1640;
24VDC output - use T2428100.
Output:
• 6VDC, 12VDC or 24VDC selectable output.
• 1.2A continuous supply current at 6VDC-12VDC.
750mA continuous supply current at 24VDC.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.3A.
• Battery short circuit protection (circuit breaker).
Visual Indicators:
• AC input and DC output LED indicators.
Features:
• Extremely compact design.
• Includes battery leads.
• Snap Track compatible
(order Altronix model number ST3).
Board Dimensions (L x W x H approx.):
3” x 2.5” x 1.5” (76.2mm x 63.5mm x 38.1mm).