- 4 - ALTV1224DCseries
ALTV1224DC1/CB Terminal Identification:
OLS127
Terminal Legend Function/Description
L, G, N 115VAC power mains connection.
– DC +
12VDC or 24VDC @ 4 amp total continuous output.
– BAT + Stand-by battery connections. Maximum charge rate .5 amp.
PD16W/PD16WCB
1P - 16P Positive DC power outputs.
1N - 16N Negative DC power outputs.
D
oor
CAUTION: De-energize unit prior to servicing. For continued protection against
fire hazard replace fuse with the same type and rating 5A, 250V.
Do not expose unit to rain or moisture.
Switch Position:
24VDC = SW1 OPEN
12VDC = SW1 CLOSED
OFF ON
Power ON/OFF
Switch
Trimpot
Wire Strap
(from
Enclosure
to Door)
2
4V - OPEN
12V - CLOSED
24V - OPEN
12V - CLOSED
3.5A 250V
For continuous protection against risk of fire
replace fuses with same type and rating.