Installation Instructions

- 2 - AL802ULADAJ
Agency Listings:
• ULListedControlUnitsforFireProtective
SignalingSystems(UL864).
• MEA-NYCDepartmentofBuildingsApproved.
• CSFM-CaliforniaStateFireMarshalApproved.
• FM-FactoryMutualApproved.
• NFPA72Compliant.
Input:
• Powerinput120VAC60Hz,5amp.
• Two(2)ClassA,StyleZortwo(2)ClassB,
StyleW,YFACPinputs.
• Two(2)NCdrycontacttriggerinputs.
Output:
• Class2Ratedpowerlimitedoutputs.
• 24VDC@8ampmaxtotalalarmcurrent.
• 2.5ampmaxcurrentperoutput.
• Separate1.0ampauxiliaryoutput.
• Programmablesupervisedindicatingcircuitoutputs:
Four(4)ClassB,StyleW,YorTwo(2)ClassA,
StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB,
StyleW,Y(see Application Guide).
•Thermalandshortcircuitprotectionwithautoreset.
Battery Backup:
•Built-inchargerforsealedleadacidorgeltypebatteries.
•Automaticswitchovertostand-bybatterywhen
ACFails.
• Zerovoltagedropwhenswitchingoverto
batterybackup.
Supervision:
•ACfailsupervision(form“C”contact,1amp/28VDC).
Factorysetfor30secondswithoptional2.5to3hour
delaysetting(fieldselectable).
• InstantlocalACtroublereportingrelay
(form“C”contact,1amp/28VDC).
•Batterypresenceandlowbatterysupervision
(form“C”contact,1amp/28VDC).
Visual Indicators:
•InputandoutputstatusLEDindicators.
Special Features:
• 2-wirehorn/strobeSyncmodeallowsaudible
notificationappliances(horns)tobesilenced
whilevisualnotificationappliances(strobes)
continuetooperate.
• SyncprotocolsincludePotter/Amseco,Faraday,
Gentex
®
,
SystemSensor
®
,andCooperWheelock
®
.
• TemporalCode3,SteadyMode,InputtoOutput
FollowerMode(maintainssynchronizationof
notificationappliancescircuit).
• Compatiblewith12VDCor24VDCfirepanels.
•Outputloopsupervisionsteeredtoinput1orinput2.
• Signalcircuittroublememory(helpsidentify
intermittentloopproblems).
• Commontroubleinputandoutput.
• Groundfaultdetection.
Added Features:
•Unitincludespowersupply,redenclosure,camlock,
andbatteryleads.
Enclosure Dimensions (approx. H x W x D):
18”x14.5”x4.625”(457.2mmx368.3mmx117.48mm)
Overview:
The Altronix AL802ULADAJ is an extremely cost effective 8 amp remote power supply/battery charger. It may be
connectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationAppliance
Circuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypower
tosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,Y
orClassA,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputwithresetforfour(4)-wiresmoke
detectorsisavailable.The8ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNAC
devices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3or
StrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput,
i.e.MarchTimeInput,MarchTimeOutput).Innon-alarmconditionindependentloopsupervisionforClassA,StyleZ
and/orClassB,StyleW,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedvia
thesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals[NC,C,NO]whichareused
toindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devices
toreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionand
powerdeliverytoanycombinationofthefour(4)outputs.
Specifications:
AL802ULADAJ - NAC Power Extender