AL802ULADAJ NAC Power Extender Installation Guide (See Application Guide for additional information) Altronix Corp. 140 58th St. Brooklyn, NY Rev.
AL802ULADAJ - NAC Power Extender Overview: The Altronix AL802ULADAJ is an extremely cost effective 8 amp remote power supply/battery charger. It may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories.
Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit. Output: Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total output current must not exceed current 8 amp in Alarm Condition. Battery: Use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries connected in series.
Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings: • For all Class B, Style W, Y, hookups SW1 & SW2 on the AL800LGK logic board must be open. For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK logic board must be closed. Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4) Switch Positions Function Descriptions ON OFF Input to Output Follower Mode 1 2, 3 Output follows signal it receives from the corresponding input (i.e.
Amount of Notification Appliances per NAC: Amseco 27 per NAC* Faraday 39 per NAC* Gentex® 32 per NAC* System Sensor® CooperWheelock® 32 per NAC* 32 per NAC* *Not to exceed a maximum of 2.5 amp per NAC AL800LGK Logic Board Terminal Legend IN1+, IN1IN2+, IN2(Supervised) Terminal Identification Table: Function/Description These terminals connect to the 12VDC or 24VDC FACP notification appliance circuit outputs. (Class A, Style Z or Class B, Style W, Y) Input trigger voltage is 8-33VDC @ 5mA min.
AL800ADA Power Supply Board* Terminal Identification Table: Terminal Legend L, G, N Function/Description + DC – 24VDC @ 8 amp in alarm non-power limited output. Connect 120 VAC to these terminals: L to hot, N to neutral. Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
Do not expose to rain or moisture. Use for Indoor Dry Location. CAUTION: De-energize prior to servicing. For continued pro Optional Hookupunit Diagram: electric shock and fire hazard replace fuse with the same type and CAUTION: De-energize unit prior to servicing. For continued protection against Divider Replace fuse cover before not expose to rain or mo electric shock and fire hazard replace fuse withenergizing. the same type andDo rating, 5 amp 250V. Fig.
Optional hookups: 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2a) to the common trouble input.
Battery Calculation Worksheet Device For each device use this formula: Number of Current per Device Devices This column x This column = Equals AL802ULADAJ (Current draw from battery) 1 A AL802 Current Auxiliary Devices Stand-by: 90mA Alarm: 175mA 90mA 175mA 90mA 175mA Refer to device manual for current ratings. Alarm/Stand-by Alarm/Stand-by Alarm/Stand-by B Stand-by Alarm Current Current Current per number of devices.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL802ULADAJ AUX output.
A.1 Four (4) Wire Smoke Detectors (cont.) Detector Type Smoke Detector/Base Max Standby Current (mA) .05 .05 .05 .05 Alarm Current (mA) 23 23 35 35 System Sensor 4W-B (12/24 volt) System Sensor 4WT-B (12/24 volt) System Sensor 4WTA-B (12/24 volt) System Sensor 4WTR-B (12/24 volt) Photoelectric I3 Photoelectric I3 w/Therm I3 Photo w/Therm/Sounder I3 Photo w/Therm/Relay System Sensor 4WTR-B (12/24 volt) I3 Photo w/Therm/ Sounder/Relay .
Enclosure Dimensions (H x W x D approximate): 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm) 14.5” (368.3mm) 1.5” (38.1mm) 2.5” (63.5mm) 2.5” (63.5mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.0” (25.4mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.5” (38.1mm) 2.5” (63.5mm) 8.5” (215.9mm) 6.0” (152.4mm) 18.0” (457.2mm) 18.0” (457.2mm) 18.0” (457.2mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.0” (25.4mm) 2.75” (69.85mm) 1.5” (38.1mm) 14.5” (368.3mm) 4.