Installation Manual

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC.Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.Shortcircuitorthermaloverloadcondition.
OFF OFF NoDCoutput.LossofAC.Dischargedornobatterypresent.
Terminal Identification:
Terminal Legend Function/Description
AC/AC LowvoltageACinput.
-DC+
12VDC@1.2ampcontinuoussupplycurrent.
24VDC@750mAcontinuoussupplycurrent.
+BAT- Stand-bybatteryconnections.Maximumchargerate300mA.
AC AC +DC -BAT +
AC
DC
FACTORY SET AT 12V
CUT J1 FOR 24V
CUT J2 FOR 6V
J1
J2
Altronixisnotresponsibleforanytypographicalerrors.Productspecicationsaresubjecttochangewithoutnotice.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IIAL624Kit-Rev.090203 H27M
MEMBER