Installation Guide
AL600ULX Series - 3 -
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and
fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
Wire
Strap
(from
Enclosure
to Door)
Battery & AC
Supervision
Circuit
(power-limited)
Class 1
Power
Distribution
Module(s)
INPUT
Divider
Earth
Ground
+ DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
AC FAIL
DCAC BAT
LG N
5A 250V
OPEN - 24V
CLOSED - 12V
AC Delay
OPEN - 24V
CLOSED - 12V
Battery
connection
(non power-limited)
(non power-limited)
(non
power-
limited)
CAUTION: Optional rechargeable stand-by batteries must match the power supply output
voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - CLOSED (Fig. 1b, pg. 3)
24VDC SW1 - OPEN (Fig. 1b, pg. 3)
Stand-by Specifications (total current shown):
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
24VDC / 12AH Battery --------
Stand-by = 200mA
Alarm = 6.0 amp
--------
24VDC / 40AH Battery
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
Installation Instructions:
WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocal
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure.Drillthelowerholesandinstalltwofasteners.Placetheenclosure’supperkeyholesoverthe two upper
screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 7-8).
Fig. 1
Fig. 1a
Fig. 1b