Installation Instructions Owner manual
LED Diagnostics:
R
ed (DC) Green (AC) Power Supply Statu
s
ON ON Normal operating condition
ON OFF Loss of AC, Stand-by battery supplying power
OFF ON No DC output
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output
Terminal Identification:
Terminal Function/Description
Legend
AC / AC Low voltage AC input (28VAC / 200VA).
Two (2) Altronix part # T2885D.
+ DC - 12VDC / 24VDC @ 6 amp continuous non-power limited output.
AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm
C, N
.C., N.O. panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 28VDC
Low Battery Used to indicate low battery condition, e.g. connect to alarm panel.
N.O
., N
.C., C Relay normally energized when DC power is present.
Contact rating 1 amp @ 28VDC
- BAT + Stand-by battery connections. Maximum charge rate .7 amp.