Installation Manual

Power Supply/Charger Boards Installation Guide
Rev. ULXB-020419
Overview:
Altronix ULXB power supply/chargers convert a 115VAC / 60Hz input to a 12VDC or 24VDC output.
Agency Listings:
Altronix
Model Number
UL Listed Sub-Assembly for
US Installations
UL Listed Sub-Assembly
for Canadian Installations
UL294*
Access
Control
UL603
Burglar
Alarm
UL1069
Hospital Signaling
and Nurse Call
UL1481
Fire Alarm
CSA C22.2 No.205-M1983
Signal Equipment
AL400ULXB2
P
P
P
P
P
AL600ULXB
N/A
AL1012ULXB
N/A N/A N/A
AL1024ULXB2
P
N/A
P
Altronix
Model Number
* ANSI/UL 294 7th Ed. Access Control Performance Levels
Destructive Attack Endurance Test Line Security Standby Power
AL400ULXB2
N/A - sub-assembly IV I II
AL600ULXB
N/A - sub-assembly IV I IV
AL1012ULXB
I I I II
AL1024ULXB2
N/A - sub-assembly IV I IV
Specifications:
Altronix
Model Number
Input Rating
115VAC 60Hz
Output Voltage (Current)
Power-Limited
Output
Maximum
Charge Current
12VDC 24VDC
AL400ULXB2
3.5A 4A 3A
P
0.7A
AL600ULXB
3.5A 6A 6A –* 0.7A
AL1012ULXB
2.6A 10A –* 0.7A
AL1024ULXB2
4.2A 10A –* 3.6A
All of the above UL Listed Sub-Assembly Power Supply/Chargers can be installed in Trove1 and Trove2 Access
and Power Integration Systems and Maximal Series.
*For UL603 applications, or if a power-limited output is required in the end-product application, the DC output
from the power supply must be connected to a separately Listed control unit or accessory board that provides
power-limited outputs. The product(s) providing the power-limited output(s) must be listed as appropriate for the
particular end-product application (fire alarm, burglar alarm, access control) and wired in accordance with the
products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-rated enclosures
all must be considered when connecting the DC output of the power supply to the end-product devices.
The auxiliary outputs of these units are power-limited.
Output:
Filtered and electronically regulated output.
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Zero voltage drop when switched over to
battery backup.
Supervision:
AC fail supervision (form “C” contacts).
Low battery and battery presence supervision
(form “C” contacts).
Visual Indicators:
AC input, DC output and BAT trouble
LED indicators.
Additional Features:
Short circuit and thermal overload protection.
Board Dimensions (L x W x H approximate):
AL400ULXB2:
7.1” x 4.5” x 1.44” (180mm x 114mm x 37mm).
AL600ULXB:
7.1” x 4.5” x 2” (180.3 mm x 114.3 mm x 50.8 mm).
AL1012ULXB:
7.25” x 4.5” x 1.75”
(184.2mm x 114.3mm x 44.5mm).
AL1024ULXB2:
8.4” x 4.5” x 1.9” (213.4mm x 114.3mm x 48.3mm).
Altronix
Model Number
Input
Rating
115VAC
60Hz
Output Voltage
(Current)
Power-
Limited
Output
Maximum
Charge
Current
UL294 Access Control Performance Levels
12VDC 24VDC
Destructive
Attack
Endurance
Test
Line
Security
Standby
Power
AL400ULXB2
3.5A 4A 3A
P
0.7A
N/A - sub-
assembly
IV I IV
AL600ULXB
3.5A 6A 6A –* 0.7A
N/A - sub-
assembly
IV I IV
AL1012ULXB
2.6A 10A –* 0.7A
N/A - sub-
assembly
IV I IV
AL1024ULXB2
4.2A 10A –* 3.6A
N/A - sub-
assembly
IV I IV

Summary of content (4 pages)