6. ForAccessControlapplicationsbatteriesareoptional.
WhenbatteriesarenotusedalossofACwillresultin
thelossofoutputvoltage.Whenuseofstand-bybatteries
isdesired,theymustbeleadacidorgeltype.
Connectbatterytotheterminalsmarked[+BAT---]
(Fig. 2).Usetwo(2)12VDCbatteriesconnected
inseriesfor24VDCoperation(batteryleadsincluded).
7. ConnectappropriatesignalingnotificationdevicestoAC
FAIL&BATFAIL(Fig. 2)supervisoryrelayoutputs.
Note:Whenusedinfirealarm,burglaralarmoraccess
controlapplications,“ACFail”relayshouldbeutilized
tovisuallyindicatethatACpowerison.Todelay
report6hourscut“ACDelay”jumper(Fig. 2a).
Maintenance:
Unitshouldbetestedatleastonceayearforthe
properoperationasfollows:
Output Voltage Test:Undernormalloadconditions,the
DCoutputvoltageshouldbecheckedforpropervoltagelevel
(refer to Power Supply Output Selections chart).
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged,checkspecified
voltagebothatthebatteryterminalandattheboardterminalsmarked[+BAT---]toensurethatthereis
nobreakinthebatteryconnectionwires.
Note:Maximumchargingcurrentunderdischargeis0.7amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
LED Diagnostics:
Red (DC) Green (AC) Red (BAT) Power Supply Status
ON ON ON Normaloperatingcondition.
ON OFF ON LossofAC,Stand-bybatterysupplyingpower.
OFF ON OFF NoDCoutput,BatteryTrouble
OFF OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
ON ON OFF Batterymissing/Low
Terminal Identification:
L,G,N Connect115VAC60Hztotheseterminals:Ltohot,Ntoneutral,Gtoground.
–DC+ 12VDC/24VDC@6ampcontinuousnonpower-limitedoutput.
ACFail
NC,C,NO
IndicateslossofACpower,e.g.connecttoaudibledeviceoralarmpanel.Relaynormallyenergized
whenACpowerispresent.Contactrating1amp@28VDC.ACorbrownoutfailisreportedwithin
1minuteofevent.Todelayreportingofupto6hrs.,cut“ACdelay”jumperandresetpowertounit.
BatFail
NC,C,NO
Indicateslowbatterycondition,e.g.connectto alarm panel. Relaynormallyenergized when DC
powerispresent.Contactrating1amp@28VDC.Aremovedbatteryisreportedwithin5minutes.
Batteryreconnectionisreportedwithin1minute.
Lowbatterythreshold:
12VDCoutputthresholdset@approximately10.5VDC,
24VDCoutputthresholdset@approximately21VDC.
+BAT--- Stand-bybatteryconnections.Maximumchargecurrent1.2amp.
+ DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
AC FAIL
DCAC BAT
LG N
5A 250V
OPEN - 24V
CLOSED - 12V
Fig. 2
Altronixisnotresponsibleforanytypographicalerrors.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IIAL600ULXB-Rev.120300 H14M
MEMBER
Fig. 2a
+ DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
AC FAIL
DCAC BAT
LG N
5A 250V
OPEN - 24V
CLOSED - 12V