Installation Guide
AL600ULX Series - 3 -
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and
fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
Wire
Strap
(from
Enclosure
to Door)
Battery & AC
Supervision
Circuit
(power-limited)
Class 1
Power
Distribution
Module(s)
INPUT
Divider
Earth
Ground
+ DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
AC FAIL
DCAC BAT
LG N
5A 250V
AC Delay
Battery
connection
(non power-limited)
(non power-limited)
(non
power-
limited)
CAUTION: Optional rechargeable stand-by batteries must match the power supply output
voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
SW1
OFF - 24V
ON - 12V
ON
OFF - 24V
ON - 12V
ON
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - ON (Fig. 1b, pg. 3)
24VDC SW1 - OFF (Fig. 1b, pg. 3)
Stand-by Specifications (total current shown):
Output
4 hr. of Stand-by and
5 Minutes of Alarm
24 hr. of Stand-by and
5 Minutes of Alarm
60 hr. of Stand-by and
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
24VDC / 12AH Battery --------
Stand-by = 200mA
Alarm = 6.0A
--------
24VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper
screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7-8).
Fig. 1
Fig. 1a
Fig. 1b