Cut Sheet
AL600ULX Series
Power Supply/Chargers
Input
Voltage 115VAC, 60Hz, 3.5A max.
Fusing 5A / 250V.
Outputs
Voltage 12VDC or 24VDC selectable.
Current 6A @ 12VDC or 24VDC continuous max.
Protection Fused 3.5A / PTC 2.5A.
Other Overvoltage protection.
Filtered and regulated.
Back-up Battery (not included)
Capacity 7AH / 12VDC (1 or 2 within enclosure).
12AH / 12VDC (requires larger “X” enclosure).
40 AH / 65 AH (requires separate enclosure).
Type Sealed lead acid or gel type.
Failover Upon AC loss, instantaneous.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Indicators (LED)
Input 115VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Agency Listings
All Models:
UL:
UL294 Access Control System Units.
UL1481 Power Supplies for
Fire Protective Signaling Systems.
cUL:
CSA C22.2 No.205 Signal Equipment.
AL600ULX and AL600ULXX only:
CSFM California State Fire Marshall Approved.
MEA NYC Department of Buildings Approved.
FM Factory Mutual Approved.
Physical and Environmental
Dimensions (H x W x D)
AL600ULX, AL600ULPD4(CB), AL600ULPD8(CB):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
AL600ULXX, AL600ULXPD16(CB):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
Product / Shipping Weight (approx.)
Model Product Weight Shipping Weight
AL600ULX 7.05 lbs. (3.2 kg) 8.9 lbs. (4.1 kg)
AL600ULXX 8.65 lbs. (3.92 kg) 10.95 lbs. (4.97 kg)
AL600ULPD4(CB) 7.2 lbs. (3.27 kg) 9.05 lbs (4.1 kg)
AL600ULPD8(CB) 7.3 lbs. (3.31 kg) 9.15 lbs (4.15 kg)
AL600ULXPD16(CB) 8.95 lbs. (4.06 kg) 11.25 lbs. (5.1 kg)
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr. (approx.):
12VDC: 37 BTU/Hr.
24VDC: 74 BTU/Hr.
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com