ACMCB Series Access Power Controllers with Power Supplies Installation Guide Models Include: • AL400ULACMCB - 4 amp @ 12VDC - or 3 amp @ 24VDC. PTC Outputs • AL1012ULACMCB - 10 amp @ 12VDC. - PTC Outputs • AL600ULACMCB - 6 amp @ 12VDC or 24VDC. - PTC Outputs • AL1024ULACMCB - 10 amp @ 24VDC. - PTC Outputs For a red enclosure, add an “R” suffix to the part # e.g. AL600ULACMCBR Rev.
Overview: These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
• Battery fail and battery presence supervision (form "C" contact). • Enclosure accommodates up to two (2) 12AH batteries. Enclosure dimensions: 15.5"H x 12"W x 4.5"D Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in desired location.
. Connect AC (Fig. 2, pg. 6): Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power limited wiring separate from non-power limited wiring (115VAC 60Hz Input, Battery Wires). Minimum .25” spacing must be provided. 5. Output options (Fig. 1, pg. 5): The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(Output Voltage and Stand-by Specification Charts, pg. 3). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [- BAT +] to insure that there is no break in the battery connection wires. Note: AL400ULXB, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
LED Diagnostics: Power Supply Board LED Red (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery. ACM8 Access Power Controller LED ON OFF LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Terminal Identification Tables: Power Supply Board Terminal Legend Function/Description L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground. - DC + AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited). AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited). AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power limited). AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power limited).
Hook-up Diagrams: Fig. 3 Optional hook-up using two (2) isolated power supply inputs: Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPER J3 CUT JUMPERS J1 AND J2 J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8CB POWER) J1 INTERFACE J3 TRG Fig. 5 Normally Open - Non-Latching FACP trigger input: Fig. 6 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) J3 INTERFACE J3 TRG N.O.
AL1024ULACMCB Battery Size Calculation Worksheet. A. AL1024ULACMCB internal current consumption (standby) ______________________ .35 A B. Load current consumption (standby) ______________________ A C. Standby time required (hours) ______________________ H D. Battery capacity required for standby (A+B)*C ______________________ AH E. AL1024ULACMCB internal power consumption (Alarm) ______________________ .35 A F. Load current consumption (Alarm) ______________________ A G.
Enclosure Dimensions: 15.5”H x 12”W x 4.5”D 4.5" TOP & BOTTOM 1.25" 0 1.5" 4.5" 1.25" 0 0 .875" 6" 10.5" 10.75" 12" 0 1.25" 4.5" 0 1" 2" 6.625" 10" 13.5" 14.25" 15.
Notes : ACMCBseries - 11 -