Data Sheet

AL600ULACM converts a 115VAC 60Hz input into eight (8) independently
controlled 12VDC or 24VDC Fail-Safe and/or Fail-Secure outputs with a total
of 6 amp continuous supply current. These power outputs can be converted
to dry form “C” contacts. Outputs are activated by an open collector sink or
normally open (NO) dry trigger input from an Access Control System, Card
Reader, Keypad, Push Button, PIR, etc. This unit will route power to a vari-
ety of access control hardware devices including Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. The outputs will operate in both Fail-Safe and/or
Fail-Secure modes. This unit is designed to be powered by one common power
source (factory installed) which will provide power for both the board operation
and locking devices, or two (2) totally independent power sources, one (1) pro-
viding power for board operation and the other for lock / accessory power. The
FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used
to trigger other auxiliary devices. The fire alarm disconnect feature is individu-
ally selectable for any or all of the eight (8) outputs.
AL600ULACM
Power Supply/Chargers with Multi-Output
Access Power Controllers
Rev. DSAL600ULACM_05152015
Overview
Specifications
Input:
Input 115VAC 60Hz rated @ 3.5 amp.
Power supply input options:
a) One (1) common power input for ACM8
and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8 and one (1) for lock accessory power,
(external power supply is required). Current is
determined by the power supply connected, not to
exceed a maximum of 10 amp total.
Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
12VDC or 24VDC @ 6 amp supply current.
Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
c) Any combination of the above.
Eight (8) auxiliary power outputs (unswitched)
Output ratings:
- Fuses are rated @ 3.5 amp.
Filtered and electronically regulated outputs
(built-in power supply).
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
Low battery and battery presence supervision
(form “C” contact).
Features:
Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1 amp 28VDC).
Short circuit and thermal overload protection.
Visual Indicators:
Red LEDs indicate outputs are triggered
(relays energized).
Green LED indicates FACP disconnect is triggered.
AC input and DC output LED indicators.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Power Supply Board maximum charge current 0.7 amp.
Automatic switch over to stand-by battery when AC fails.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Electrical:
Operating temperature: 0º C to 49º C ambient.
ACM8 board main fuse is rated at 10 amp.
• BTU/Hr.:
- 12VDC: 36.85 BTU/Hr.
- 24VDC: 73.70 BTU/Hr.
Mechanical:
Enclosure Dimensions (L x W x H approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
Enclosure accommodates up to two (2) 12AH batteries.
Product weight (approx.): 10.3 lbs. (4.67 kg).
Shipping weight (approx.): 11.6 lbs. (5.26 kg).
AL600ULACM

Summary of content (2 pages)