Installation Instructions
AL600X220 Series Installation Guide - 3 -
Stand-by Specifications (total current shown):
Output
4 hr. of Stand-by and
5 Minutes of Alarm
24 hr. of Stand-by and
5 Minutes of Alarm
60 hr. of Stand-by and
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
24VDC / 12AH Battery –
Stand-by = 200mA
Alarm = 6.0A
–
24VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
Switch Position:
24VDC = SW1 OFF
12VDC = SW1 ON
Battery & AC
Supervision Circuit
(power-limited)
J1
AC Delay
Power
Distribution
Module(s)
BAT FAIL NC C NO NC C NO
AC FAIL
AC DC BAT
+BAT-
+ DC -
L G N
OFF - 24V
ON - 12V
ON
Ground
Lug
220VAC
power mains
non power-limited
Battery connection
(non power-limited)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
For 12VDC Operation
use hook-up in the
inset on the right
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
OFF - 24V
ON - 12V
SW1
ON
1
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
J1
AC Delay
Battery & AC
Supervision Circuit
NC C NO NC C NO
Fig. 1a
Fig. 1c
Fig. 1b
Fig. 1 - AL600X220 Series