AL400ULX Series Power Supply/Charger Installation Guide Models Include: • AL400ULX - Single Output • AL400ULPD4 • AL400ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs • AL400ULPD8 • AL400ULPD8CB - Eight (8) Fused Outputs - Eight (8) PTC Outputs • AL400ULXPD16 • AL400ULXPD16CB - Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs For a red enclosure, add an “R” suffix to the part # e.g. AL400ULPD8R Rev.
Overview: The AL400ULX is a power supply that converts a 115VAC / 60Hz input, to a 12VDC or 24VDC regulating output, (see specifications below). The AL400ULX is the base power supply unit for the UL Listed multi-output power supply/charger series: AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16, AL400ULXPD16CB (Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
Stand-by Specifications (total current shown): Output 12VDC / 40AH Battery 4 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 4.0 amp Alarm = 4.0 amp 24VDC / 12AH Battery -------- 24VDC / 40AH Battery Stand-by = 3.0 amp Alarm = 3.0 amp 24 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 1.0 amp Alarm = 4.0 amp Stand-by = 200mA Alarm = 3.0 amp Stand-by = 1.0 amp Alarm = 3.0 amp 60 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 300mA Alarm = 4.0 amp -------Stand-by = 300mA Alarm = 3.
Installation Instructions (cont’d): 2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC / 60Hz to terminals marked [L, G, N] (Fig. 1, pg. 3). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
Terminal Identification: Power Supply Board Terminal Legend L, G, N + DC --- Function/Description Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral, G to ground. 12VDC @ 4 amp or 24VDC @ 3 amp continuous power limited output. Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL400ULX output.
Enclosure Dimensions (BC300): AL400ULX, AL400ULXR, AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB 13.5”H x 13”W x 3.
Enclosure Dimensions (BC400): AL400ULXX, AL400ULXPD16, AL400ULXPD16CB 15.5”H x 12.23”W x 4.5”D 1.500" 4.615" 4.615" 1.500" 1.750" 1.375" 1.125" 4.500" 12.230" 1.250" 4.500" 1.100" 1.250" 1.100" 0.910" 0.910" 1.500" 1.500" 2.000" 15.500" 2.000" 5.000" 5.000" 0.790" 1.250" 1.100" 1.250" 1.750" 1.500" 4.615" 4.615" 1.500" Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.