Installation Instructions Instruction Manual
7. ConnectappropriatesignalingnotificationdevicestoACFAIL&BATFAIL(Fig. 2, pg. 2) supervisory relay outputs.
Note:Whenusedinfirealarm,burglaralarmoraccesscontrolapplications,“ACFail”relayshouldbe
utilized to visually indicate that AC power is on. Todelayreport6hourscut“ACDelay”jumper(Fig. 2a, pg. 2).
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(refer to Power Supply Voltage Output Specifications chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the
battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery
connection wires.
Note:Maximumchargingcurrentunderdischargeis0.7amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat) Battery Status
ON Normal operating condition.
OFF Battery fail/low battery.
Terminal Identification:
Terminal Legend Function/Description
L, G, N Connect115VAC60Hztotheseterminals:Ltohot,NtoNeutral,Gtoground.
+ DC --- 12VDC@4ampor24VDC@3ampcontinuouspower-limitedoutput.
AC Fail
NC, C, NO
IndicateslossofACpower,e.g.connecttoaudibledeviceoralarmpanel.Relaynormallyenergized
whenACpowerispresent.Contactrating1amp@28VDC.ACorbrownoutfailisreportedwithin
1minuteofevent.Todelayreportingofupto6hrs.,cut“ACdelay”jumperandresetpowertounit.
Bat Fail
NC, C, NO
Indicateslowbatterycondition,e.g.connecttoalarmpanel.Relaynormallyenergized
whenDCpowerispresent.Contactrating1amp@28VDC.
+ BAT --- Stand-bybatteryconnections.Maximumchargecurrent0.7amp.
Altronixisnotresponsibleforanytypographicalerrors.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IIAL400ULXB2-Rev.101112 H15M
Fig. 2
MEMBER
+ DC ---
NC C NO NC C NO
+
BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
Opened - 24V
Closed - 12V
AC FailBat Fail
J1
SW1
5A 250V
15A 250V
AC Delay
15
L G N
Fig. 2a
+ DC ---
NC C NO NC C NO
+ BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
Opened - 24V
Closed - 12V
AC FailBat Fail
J1
SW1
5A 250V
15A 250V
AC Delay
15
L G N