AL400ULX Series Power Supply/Charger Installation Guide Models Include: • AL400ULX - Single Output • AL400ULPD4 • AL400ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs • AL400ULPD8 • AL400ULPD8CB - Eight (8) Fused Outputs - Eight (8) PTC Outputs • AL400ULXPD16 • AL400ULXPD16CB - Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs For a red enclosure add an “R” suffix to the part # e.g. AL400ULPD8R Rev.
Overview: The AL400ULX is a power supply that converts a 115VAC / 60Hz input to a 12VDC or 24VDC regulating output (see specifications below). The AL400ULX is the base power supply unit for the UL Listed multi-output power supply/charger series: AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16, AL400ULXPD16CB (Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
Stand-by Specifications (total current shown): 4 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 4.0A Alarm = 4.0A Output 12VDC / 40AH Battery 24VDC / 12AH Battery -------- 24VDC / 40AH Battery Stand-by = 3.0A Alarm = 3.0A 24 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 1.0A Alarm = 4.0A Stand-by = 200mA Alarm = 3.0A Stand-by = 1.0A Alarm = 3.0A 60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 4.0A -------Stand-by = 300mA Alarm = 3.
Installation Instructions (cont’d): 2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead. Connect unswitched AC power (115VAC / 60Hz) to the terminals marked [L, N] (Fig. 1, pg. 3). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
Terminal Identification: Power Supply Board Terminal Legend L, G, N + DC --- Function/Description Connect 115VAC 60 Hz. to these terminals: L to Hot, N to Neutral. Do not use the [G] terminal. 12VDC @ 4A or 24VDC @ 3A continuous power-limited output. Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL400ULX output.
Enclosure Dimensions (BC300): AL400ULX, AL400ULXR, AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.
Enclosure Dimensions (BC400): AL400ULXX, AL400ULXXR, AL400ULXPD4, AL400ULXPD4CB, AL400ULXPD8, AL400ULXPD8CB AL400ULXPD16, AL400ULXPD16CB 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.