Data Sheet

Specifications
Input:
Input 115VAC, 60Hz, 3.5 amp.
Input fuse rated @ 3.5 amp/250V.
Output:
12VDC or 24VDC selectable output.
12VDC @ 4 amp or 24VDC @ 3 amp supply current.
Four (4) Class 2 Rated PTC protected power-
limited outputs.
Outputs are rated @ 2.5 amp.
Filtered and electronically regulated outputs.
Short circuit and thermal overload protection.
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Maximum charge current 0.7 amp.
Supervision:
AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
Low battery supervision (form “C” contacts).
Battery presence supervision (form “C” contacts).
Visual Indicators:
AC input and DC output LED indicators.
Electrical:
Operating temperature: 0º C to 49º C ambient.
24.57 or 36.85 BTU/Hr.
System AC input VA requirement: 402.5VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2) 12VDC/7AH batteries.
Product weight (approx.): 7.3 lbs. (3.31 kg).
Shipping weight (approx.): 8.4 lbs. (3.81 kg).
AL400ULPD4CB is a multi-output power supply/charger that converts a
115VAC/60Hz input into four (4) Class 2 Rated 12VDC or 24VDC power-
limited outputs.
AL400ULPD4CB
Multi-Output Power Supply/Charger
Rev. DSAL400ULPD4CB_05052015
Overview
Agency Approvals
UL 294 UL Listed for Access Control System Units.
UL 603 UL Listed Standard for Power Supplies for Use with Burglar Alarm Systems.
UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for Fire Protective Signaling Systems.
General Signaling Equipment
Evaluated to CSA Standard C22.2 No.205-M1983
AL400ULPD4CB

Summary of content (2 pages)