Installation Instructions

- 2 - AL400X220 Series Installation Guide
Overview:
Altronix AL400X220 is a power supply that converts a nominal 220VAC (working range 198VAC-256VAC),
50/60Hz input to a 12VDC or 24VDC regulating output (see specifications below). The AL400X is the base power
supply unit for the multi-output power supply/charger series: AL400PD4220, AL400PD4CB220, AL400PD8220,
AL400PD8CB220, AL400XPD16220, AL400XPD16CB220 (Refer to AL400X220 Series Power Supply
Configuration Reference Chart below).
AL400X220 Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of
Outputs
Fused Outputs
PTC Outputs
(auto-resettable)
12VDC Total
Output Current (A)
24VDC Total
Output Current (A)
Individual
Output
Rating (A)
Power
Supply
Input
Fuse
Rating
Power
Supply
Battery
Fuse
Rating
Accommodates
Stand-by Batteries
AL400X220
1
4A 3A
4A (12VDC)
3A (24VDC)
5A/
250V
15A/
32V
Two (2) 12VDC/7AH
AL400XX220
Two (2) 12VDC/12AH
AL400PD4220
PD4
4
P
3.5A (12VDC)
3A (24VDC)
Two (2) 12VDC/7AH
AL400XPD4220
Two (2) 12VDC/12AH
AL400PD4CB220
PD4CB
P
2.5A
Two (2) 12VDC/7AH
AL400XPD4CB220
Two (2) 12VDC/12AH
AL400PD8220
PD8
8
P
3.5A (12VDC)
3A (24VDC)
Two (2) 12VDC/7AH
AL400XPD8220
Two (2) 12VDC/12AH
AL400PD8CB220
PD8CB
P
2.5A
Two (2) 12VDC/7AH
AL400XPD8CB220
Two (2) 12VDC/12AH
AL400XPD16220
Two PD8
16
P
3.5A (12VDC)
3A (24VDC)
Two (2) 12VDC/12AH
AL400XPD16CB220
Two
PD8CB
P
2.5A Two (2) 12VDC/12AH
Do not exceed total output rating of 4A @ 12VDC or 3A @ 24VDC per unit.
Specifications:
Agency Listing:
CE European Conformity.
Input:
Input 220VAC (working range 198 - 256VAC),
50/60Hz, 1.7A.
AC input and DC output LED indicators.
Output:
12VDC or 24VDC selectable output.
4A total supply current at 12VDC or
3A total supply current at 24VDC.
Filtered and electronically regulated outputs.
Short circuit and thermal overload protection.
Battery fuse rated at 15A/32V.
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Maximum charge current 0.7A.
Zero voltage drop when switched over to
battery backup.
Supervision:
AC fail supervision (form “C” contacts).
Low battery and battery presence supervision
(form “C” contacts).
Additional Features:
Power supply, enclosure, cam lock, and battery leads.
Enclosure Dimensions:
AL400X220, AL400XR220, AL400PD4220,
AL400PD4CB220, AL400PD8220,
AL400PD8CB220:
13.5” x 13” x 3.25”
(342.99mm x 330.2mm x 82.6mm)
AL400XX220, AL400XPD4220,
AL400XPD4CB220, AL400XPD8220,
AL400XPD8CB220, AL400XPD16220,
AL400XPD16CB220:
15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm)