AL300ULX Series Power Supply/Charger Installation Guide Models Include: • AL300ULX - Single Output • AL300ULPD4 • AL300ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs • AL300ULPD8 • AL300ULPD8CB - Eight (8) Fused Outputs - Eight (8) PTC Outputs • AL300ULXPD16 • AL300ULXPD16CB - Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs For a red enclosure, add an “R” suffix to the part # e.g. AL300ULPD8R Rev.
Overview: The AL300ULX is a power supply that converts a 115VAC, 60Hz input, to a 12VDC or 24VDC regulating output (see specifications below). The AL300ULX is a base power supply unit for the UL Listed multi-output power supply/charger series: AL300ULPD4, AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB, AL300ULXPD16, AL300ULXPD16CB (Refer to AL300ULX Series Power Supply Configuration Reference Chart below). AL300ULPD4 PD4UL AL300ULPD8 x ----- PD4ULCB ----- x PD8UL PD8ULCB 3.5 2.5 2.
Stand-by Specifications (total current shown): Output 12VDC / 40AH Battery 4 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 2.5 amp Alarm = 2.5 amp 24VDC / 12AH Battery -------- 24VDC / 40AH Battery Stand-by = 2.5 amp Alarm = 2.5 amp 24 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 1.0 amp Alarm = 2.5 amp Stand-by = 200mA Alarm = 2.5 amp Stand-by = 1.0 amp Alarm = 2.5 amp 60 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.5 amp -------Stand-by = 300mA Alarm = 2.
Installation Instructions (cont’d): 2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 3) to the appropriate position (Power Supply Output Specification Chart, pg. 2). 3. Secure cabinet to earth gourd. Connect AC power (115VAC / 60 Hz to terminals marked [L, G, N] (Fig. 1, pg. 3). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power limited circuits (AC fail/Low Battery reporting).
LED Diagnostics: Power Distribution Module Green ON OFF Power Distribution Module Status. Normal operating condition. No Power Output. Terminal Identification: Power Distribution Module Terminal Legend PD4UL/PD4ULCB PD8UL/PD8ULCB 1P to 4P 1P to 8P 1N to 4N 1N to 8N Function/Description Positive DC power outputs. Negative DC power outputs. Power Distribution Module(s): Fig. 2b Fig. 2a Replace fuses with the same type and rating 3.5A, 250V.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL300ULX output.
Enclosure Dimensions (BC300): AL300ULX, AL300ULXR, AL300ULPD4, AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB 13.5” (342.99mm) x 13” (330.2mm) x 3.25” (82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.
Enclosure Dimensions (BC400): AL300ULXX, AL300ULXPD16, AL300ULXPD16CB 15.5” (393.7mm) x 12” (304.8mm) x 4.5” (114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.5” (393.7mm) 2.0” (50.8mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.1” (27.