Installation Manual
AL300ULX Series - 3 -
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - ON
24VDC SW1 - OFF
Stand-by Specifications (total current shown):
Output
4 hr. of Stand-by and
5 Minutes of Alarm
24 hr. of Stand-by and
5 Minutes of Alarm
60 hr. of Stand-by and
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 2.5A
Alarm = 2.5A
Stand-by = 1.0A
Alarm = 2.5A
Stand-by = 300mA
Alarm = 2.5A
24VDC / 12AH Battery –
Stand-by = 200mA
Alarm = 2.5A
–
24VDC / 40AH Battery
Stand-by = 2.5A
Alarm = 2.5A
Stand-by = 1.0A
Alarm = 2.5A
Stand-by = 300mA
Alarm = 2.5A
ON
OFF - 24V
ON - 12V
Door
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.
Battery connection (non power-limited)
Switch Position:
24VDC = SW1 OFF
12VDC = SW1 ON
Wire
Strap
(from
Enclosure
to Door)
Battery & AC
Supervision
Circuit
(power-limited)
For 12VDC Operation
use hook-up in the
inset on the right
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
115VAC
power mains
non power-
limited
Green
Lead
Class 1
+ DC ---
+ BAT ---
AC DC Bat
Risk of Fire,
Replace Fuses
As Marked
OFF - 24V
ON - 12V
J1
SW1
OFF - 24V
ON - 12V
SW1
5A 250V
15A 250V
AC Delay
15
L G N
NC C NO NC C NO AC FailBat Fail
DC Output to devices
(power limited)
NC C NO NC C NO
Battery & AC
Supervision Circuit
(power-limited)
J1
AC Delay
ON
1
ON
1
Fig. 1
Fig. 1a
Fig. 1b
Fig. 1c