Data Sheet
Specifications
Input:
• Input 115VAC, 60Hz, 3.5 amp.
• Input fuse rated @ 3.5 amp/250V.
Output:
• 12VDC or 24VDC selectable output.
Burglar Alarm Applications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
• 2.5 amp total supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
Visual Indicators:
• AC input, DC output and Battery LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr. :
12VDC: 14.71 - 16.63 BTU/Hr.
24VDC: 29.43 - 32.41 BTU/Hr.
• System AC input VA requirement: 402.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2) 12VDC/7AH batteries.
• Product weight (approx.): 8.7 lbs. (3.95 kg).
• Shipping weight (approx.): 9.6 lbs. (4.35 kg).
AL300ULPD8 is a multi-output power supply/charger that converts a
115VAC/60Hz input into eight (8) Class 2 Rated 12VDC or 24VDC power-
limited outputs.
AL300ULPD8
Multi-Output Power Supply/Charger
Rev. DSAL300ULPD8_05042015
Overview
AL300ULPD8
Agency Approvals
UL 294 UL Listed for Access Control System Units.
UL 603 UL Listed Standard for Power Supplies for Use with Burglar Alarm Systems.
UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for Fire Protective Signaling Systems.
General Signaling Equipment
Evaluated to CSA Standard C22.2 No.205-M1983