Installation Guide
- 2 - AL300ULX series
Overview:
The AL300ULX is a power supply that converts a 115VAC, 60Hz input to a 12VDC or 24VDC regulating output (see
specifications below).
The AL300ULX is a base power supply unit for the UL Listed multi-output power supply/charger series: AL300ULPD4,
AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB, AL300ULXPD16, AL300ULXPD16CB (Refer to AL300ULX
Series Power Supply Configuration Reference Chart below).
AL300ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
Total Output
Rating (A)
Output Rating (A)
per Output
Power Supply
Input Fuse Rating
Power Supply
Output Fuse Rating
Agency Listings
UL Listings and
File Numbers
AL300ULX
AL300ULXX
AL300ULXR
----- 1 ----- ----- 2.5 2.5
5A/
250V
15A/
32V
UL File # S4707
UL 294
UL Listed for Access Control
System Units.
UL 603
UL Listed for Power Supplies for
Use with Burglar-Alarms Systems.
UL 1069
UL Listed Hospital Signaling and
Nurse Call Equipment.
UL 1481
UL Listed for Power Supplies for
Fire Protective Signaling Systems
“Signal Equipment”
Evaluated to
CSA Standard C22.2
No.205-M1983
AL300ULPD4
PD4UL
4
x -----
2.5
3.5
5A/
250V
15A/
32V
AL300ULPD4CB
PD4ULCB ----- x 2.5
AL300ULPD8
PD8UL
8
x -----
2.5
3.5
5A/
250V
15A/
32V
AL300ULPD8CB
PD8ULCB ----- x 2.5
AL300ULXPD16
Two (2)
PD8UL
16
x -----
2.5
3.5
5A/
250V
15A/
32V
AL300ULXPD16CB
Two (2)
PD8ULCB
----- x 2.5
Specifications:
Input:
• Input 115VAC, 60Hz, 3.5A.
• AC input and DC output LED indicators.
Output:
• Class 2 Rated power-limited output(s).
• 12VDC or 24VDC selectable output(s).
Burglar Alarm Aplications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
• 2.5A total supply current.
• Filtered and electronically regulated output(s).
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.7A.
• Zero voltage drop when switched over to battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).
Additional Features:
• Power supply, enclosure, cam lock and battery leads.
• All models are available in red enclosure
(add an “R” suffix to the part # e.g. AL300ULPD8R).
Altronix Corp.
140 58th St. Brooklyn, NY
California
State Fire
Marshal
NYC
Dept. of
Buildings
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - ON
24VDC SW1 - OFF
ON
OFF - 24V
ON - 12V