AL300ULX Series Power Supply/Charger Installation Guide Models Include: • AL300ULX - Single Output • AL300ULPD4 • AL300ULPD4CB • AL300ULPD8 • AL300ULPD8CB • AL300ULXPD16 • AL300ULXPD16CB - Four (4) Fused Outputs - Four (4) PTC Outputs - Eight (8) Fused Outputs - Eight (8) PTC Outputs - Sixteen (16) Fused Outputs - Sixteen (16) PTC Outputs For a red enclosure add an “R” suffix to the part #, e.g. AL300ULPD8R Rev.
Overview: The AL300ULX is a power supply that converts a 115VAC, 60Hz input to a 12VDC or 24VDC regulating output (see specifications below). The AL300ULX is a base power supply unit for the UL Listed multi-output power supply/charger series: AL300ULPD4, AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB, AL300ULXPD16, AL300ULXPD16CB (Refer to AL300ULX Series Power Supply Configuration Reference Chart below).
Stand-by Specifications (total current shown): 4 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 2.5A Alarm = 2.5A Output 12VDC / 40AH Battery 24VDC / 12AH Battery -------- 24VDC / 40AH Battery Stand-by = 2.5A Alarm = 2.5A 24 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 1.0A Alarm = 2.5A Stand-by = 200mA Alarm = 2.5A Stand-by = 1.0A Alarm = 2.5A 60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.5A -------Stand-by = 300mA Alarm = 2.
Installation Instructions (cont’d): 2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 3) to the appropriate position (Power Supply Output Specification Chart, pg. 2). 3. Secure cabinet to earth ground. Connect AC power (115VAC / 60 Hz to the terminals marked [L, N] (Fig. 1, pg. 3). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC fail/Low Battery reporting).
Terminal Identification: Power Supply Board Terminal Legend Function/Description L, G, N Connect 115VAC 60Hz. to these terminals: L to Hot, N to Neutral. Do not use the [G] terminal. + DC --12VDC or 24VDC @ 2.5A continuous power-limited output. Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will report approximately AC Fail within one (1) minute after loss of AC.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL300ULX output.
Enclosure Dimensions (BC300): AL300ULX, AL300ULXR, AL300ULPD4, AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.20” (31mm) 3.25” (83mm) 1.20” (31mm) 0.75” (19mm) 12.5” (318mm) 11.0” (279mm) 1.20” (31mm) 0.75” (19mm) 0.9375” (24mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 0.9375” (24mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.
Enclosure Dimensions (BC400): AL300ULXX, AL300ULXXR, AL300ULXPD4, AL300ULXPD4CB, AL300ULXPD8, AL300ULXPD8CB, AL300ULXPD16, AL300ULXPD16CB 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 1.25” (31.75mm) 4.5” (114.3mm) 12.23” (310.64mm) 1.1” (27.94mm) 0.91” (23.114mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.1” (27.94mm) 1.25” (31.75mm) 0.91” (23.114mm) 2.0” (50.8mm) 1.5” (38.1mm) 15.