Installation Instructions
AL125ULseries - 1 -
*Note: When unit is powered by battery back up (AC Fail condition), the voltage range is 9.3V-13.2V and
19.55V-26.4V for 12 and 24 volt operation respectively.
Power Supply Output Specifications: (AL125UL, AL125ULX)
Output VDC Switch Position Max. Stand-by Load DC Max. Alarm Load DC Battery (optional)
12VDC SW2 OFF 1 amp 1 amp 12VDC
24VDC SW2 ON 1 amp 1 amp 24VDC
Power Supply Output Specifications: (AL125ULP, AL125ULE)
Output VDC Switch Position Max. Stand-by Load DC Max. Alarm Load DC Battery (optional)
12VDC SW2 OFF 1 amp 1 amp 12VDC
24VDC SW2 ON 0.5 amp 0.5 amp 24VDC
Stand-by Specifications:
Output
4hr. of Stand-by &
5 min. of Alarm
Output
4hr. of Stand-by &
5 min. of Alarm
12VDC / 4AH Battery 0.5 amp / 1 amp 12VDC / 7AH Battery 1 amp / 1 amp
24VDC / 4AH Battery 0.5 amp / 1 amp 24VDC / 7AH Battery 1 amp / 1 amp
Agency Listings:
• UL Listed for Access Control Systems (UL294).
CUL Listed - CSA Standard C22.2 No.205-M1983,
Signal Equipment.
• MEA - NYC Department of Buildings Approved.
• NFPA 101 (Life Safety).
Input:
• AL125UL, AL125ULX - 115VAC 50/60 Hz, 0.6 amp.
• AL125ULP, AL125ULE - 24VAC @ 40VA.
Output:
• Two (2) 12VDC or 24VDC, Class 2 Rated
Power-Limited Outputs.
• 1 amp total supply current @ 12VDC or 24VDC
(AL125UL & AL125ULX).
• 1 amp total supply current @ 12VDC, 0.5 amp total
supply current @ 24VDC (AL125ULP & AL125ULE).
• Filtered and electronically regulated output.*
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current: 400mA.
• Automatic switch over to stand-by battery when AC fails.
Special Features:
• AC power and unit status indicator on the front panel.
• Normally Open [NO] trigger input.
• Supervised Fire Alarm Disconnect (Latching w/reset
or Non-Latching).
Configurations:
• AL125UL - includes power supply, transformer
cam lock and enclosure (8.5”H x 7.5”W x 3.5”D)
(215.9mm H x 190.5mm W x 88.9 Dmm).
Accommodates one (1) 12VDC/4AH battery.
• AL125ULP - includes power supply, plug-in transformer
(24VAC/40VA) cam lock and enclosure
(8.5”H x 7.5”W x 3.5”D). Accommodates one (1)
12VDC/7AH battery or two (2) 12VDC/4AH batteries.
• AL125ULE - includes power supply, cam lock
and enclosure (8.5”H x 7.5”W x 3.5”D).
Accommodates up to two (2) 12VDC/4AH batteries.
• AL125ULX - includes power supply, transformer,
cam lock and enclosure (13.5”H x 13”W x 3.25”D)
(342.9mm H x 330.2mm W x 82.55mm D).
Accommodates up to two (2) 12VDC/7AH batteries.
Overview:
AL125UL Series power-limited Power Supply/Chargers convert 115VAC 50/60Hz input into two individually PTC pro-
tected 12VDC or 24VDC outputs (see specifications). They are intended for use in applications requiring UL Listing for
Access Control (UL294) and applications requiring an interface with Fire Alarm Control Panels.
Specifications:
AL125UL • AL125ULX • AL125ULP • AL125ULE
Access Control Power Supply/Chargers