Installation Instructions Owner's manual

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC,Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
Terminal Identification:
Terminal Legend Function/Description
L,G,N Connect115VACtotheseterminals:Ltohot,Ntoneutral.
+DC--
24VDC@8ampcontinuous,10ampinalarmnonpower-limitedoutput(UL1481).24VDC@10
amp(UL294).
ACFAIL
NO,C,NC
UsedtonotifylossofACpower,e.g.connecttoaudibledeviceoralarmpanel.Relaynormally
energizedwhenACpowerispresent.Contactrating1amp@28VDC.ACorbrownoutfailis
reportedwithin1minuteofevent.Todelayreportingofupto6hrs.,cut“ACDelay”jumperand
resetpowertounit(Fig. 1a, above).
BATFAIL
NO,C,NC
Usedtoindicatelowbatterycondition,e.g.connecttoalarmpanel.Relaynormallyenergized
whenDCpowerispresent.Contactrating1amp@28VDC.Aremovedbatteryisreported
within1minute.Batteryreconnectionisreportedwithin1minute.
Lowbatterythreshold:@approximately21VDC.
--BAT+ Stand-bybatteryconnections.Maximumchargecurrent3.6amp.
CAUTION:Forcontinuesprotectionagainstriskoffirereplacefuseswiththesametypeandrating:
InputFuseis5A/250V,BatteryFuseis15A/32V
AltronixCorp.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IIAL1024ULXB2 H30M