Data Sheet
Input:
• Input 115VAC, 60Hz, 4.2 amp.
• Input fuse rated @ 3.5 amp/250V.
• Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input.
Output:
• 24VDC outputs.
• 10 amp supply current.
• Five (5) PTC protected Class 2 Rated power-limited
outputs, rated @ 2 amp.
• Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
• Power fail supervision relay (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators
(power supply board).
• Red LEDs indicate condition of power outputs
(multi-output board).
• Power and input trigger LEDs (multi-output board).
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• 122.84 BTU/Hr.
• System AC input VA requirement: 483VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
• Product weight (approx.): 10.8 lbs. (4.90 kg).
• Shipping weight (approx.): 11.8 lbs. (5.35 kg).
Specifications
AL1024ULM
Multi-Output Power Supply/Charger
Rev. DSAL1024ULM _05212015
AL1024ULM multi-output access control power supply/charger is specifically
designed for use with access control systems and accessories. This unit con-
verts a 115VAC, 60Hz input into five (5) individually protected Class 2 Rated
power-limited 24VDC outputs. Each output will route power to a variety of ac-
cess control hardware devices including Mag Locks, Electric Strikes, Magnetic
Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure
modes. Controlled trigger input is achieved through normally open (N.O.) or
normally closed (N.C.) supervised input or the polarity reversal from an FACP
(Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shut-
down, Elevator Recall or it may be used to trigger auxiliary devices.
Overview
AL1024ULM
Agency Approvals
UL 294 UL Listed for Access Control
System Units.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.
CUL Listed - CSA Standard C22.2
No.205-M1983, Signal Equipment.
Altronix Corp.
140 58th St. Brooklyn, NY
CSFM - California State Fire
Marshal Approved.