Installation Instructions

- 8 - AL1024NKA8(D) Installation Guide
Fig. 6 - AL1024NKA8(D)
Supervision and
FACP Interface
(power-limited)
DC Output to devices
(AL1024NKA8 - non power-limited, AL1024NKA8D - power-limited)
Independently controlled Input Triggers
PTC
Protected
Outputs on
AL1024NKA8D
PWR1
+
PWR2
+
COM -
COM -
PWR2
+
PWR1
+
+ PWR2
--
+ PWR1
--
INP Logic
NO
<-->
NC
FACP
EN
<-->
DIS
FACP
FACP
FACP
Power 2
Power 1
+INP2--+INP1--+INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ONON
NC RST EOL +F +R
C GND GND -F -R
NO C NC COM NO C NC COM
Output 1Output 2
NO C NC COM NO C NC COM
Output 3Output 4
NO C NC COM NO C NC COM
Output 5 Output 6
NO C NC COM NO C NC COM
Output 7 Output 8
Tamper Switch
ACMS8(CB)
Power Output
Factory wired to
ACMS8(CB) and VR6
(non power-limited)
24VDC from
AL1024ULXB2
12VDC from VR6
(mounted under
ACMS8(CB)
Battery Output
(non power-limited)
AL1024ULXB2
Power Supply
L
G
N
BAT FAIL
AC FAIL
NC
C
NO
NC
C
NO
AC
DC
- BAT +
+ DC -
AC DELAY
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
CAUTION: Use two (2) 12VDC stand-by batteries.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25” spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure.
A UL listed external battery enclosure must be used if using
40AH or 65AH batteries.
Tamper Switch
(not included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Fig. 6a