Installation Instructions
AL1024NKA8(D) Installation Guide - 7 -
LED Diagnostics:
AL1024ULXB2 - Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
ACMS8 and ACMS8CB Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) de-energized. Output relay(s) energized.
FACP FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Green Output 1-8 12VDC –
Red Output 1-8 24VDC –
Terminal Identification:
AL1024ULXB2 - Power Supply Board
Terminal Legend Function/Description
L, N Connect 115VAC to these terminals: L to hot, N to neutral (Fig. 4a, pg. 6).
+ DC – Factory connected to ACMS8(CB) (Fig. 4d, pg. 6).
AC Fail
NC, C, NO
Used to notify loss of AC power, e.g.connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.
AC or brownout fail is reported within 1 minute of event.
To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit
(Fig. 4f, pg. 6).
Bat Fail
NC, C, NO
Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present. Contact rating 1A @ 28VDC.
A removed battery is reported within 1 minute.
Battery reconnection is reported within 1 minute.
Low battery threshold: approximately 21VDC (Fig. 4b, pg. 6).
– BAT + Stand-by battery connections. Maximum charge current 3.6A (Fig. 4c, pg. 6).
ACMS8 and ACMS8CB Access Power Controller
Terminal Legend Function/Description
+ PWR1 – Factory connected to AL1024ULXB2. Do not use these terminals.
+ PWR2 – Factory connected to VR6 voltage regulator. Do not use these terminals.
+ INP1 – through
+ INP8 –
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
C, NC
FACP Dry NC output rated 1A/28VDC @ 0.6 Power Factor. Class 2 power-limited.
With EOL JMP intact, will provide 10k resistance in a normal state.
GND, RST
FACP interface latching or non-latching. NO dry input. Class 2 power-limited.
To be shorted for non-latching FACP interface or Latch FACP reset.
GND, EOL
EOL Supervised FACP Input terminals for polarity reversal FACP function.
Class 2 power-limited.
– F, + F, – R, + R FACP Signaling Circuit Input and Return terminals. Class 2 power-limited.
Output 1 through
Output 8
NO, C, NC, COM
Eight (8) selectable independently controlled outputs [Fail-Safe (NC) or Fail-Secure
(NO)] and eight (8) independently controlled Form “C” Relay outputs.