Installation Instructions

AL1024NKA8(D) Installation Guide - 3 -
Specifications:
Inputs:
AL1024ULXB2:
115VAC, 60Hz, 4.2A.
ACMS8/ACMS8CB:
Eight (8) trigger inputs:
a) Normally open (NO) inputs (dry contacts).
b) Normally closed (NC) inputs (dry contacts).
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor
e) Any combination of the above.
Outputs:
Power:
12VDC or 5VDC up to 6A, 24VDC up to 10A
(240W total power).
Overvoltage protection.
ACMS8:
Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 6A max.
Do not exceed the individual power supply ratings.
ACMS8CB:
PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 6A max.
Do not exceed the individual power supply ratings.
Eight (8) selectable independently controlled
outputs or eight (8) indepently controlled
Form “C” relay outputs (see below for ratings):
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” relays rated @ 2.5A. 12, 24VDC,
0.6 Power Factor (ACMS8 only).
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Individual outputs may be set to OFF position for
servicing (output jumper set to middle position).
Does not apply to Dry Contact applications.
Any of the eight (8) fuse/PTC protected power
outputs are selectable to follow power Input 1 or
Input 2. Output voltage of each output is the same
as the input voltage of the input selected.
Surge suppression.
Fuse/PTC Ratings:
AL1024ULXB2:
- Input fuse is rated 5A/250V.
- Battery fuse rated 15A/32V.
ACMS8:
- Main input fuse is rated 15A/32V.
- Output fuses are rated 3A/32V.
ACMS8CB:
- Main input PTC is rated 9A.
- Output PTCs are rated 2A.
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Maximum charge current 3.6A.
Zero voltage drop when switched over to
battery backup.
Supervision:
AC fail supervision (form “C” contacts).
Low battery supervision (form “C” contacts).
Battery presence supervision (form “C” contacts).
Fire Alarm Disconnect:
Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open [NO] or normally closed [NC]
dry contact input. Polarity reversal input from
FACP signaling circuit.
FACP input WET is rated 5-30VDC 7mA.
FACP input EOL requires 10K end of line resistor.
FACP output relay [NC]:
Either Dry 1A/28VDC, 0.6 Power Factor or
10K resistance with [EOL JMP] intact.
Visual Indicators:
AL1024ULXB2:
Green AC LED: Indicates 115VAC present.
Red DC LED: Indicates DC output.
ACMS8(CB):
Red LEDs: Indicate outputs are triggered.
Blue LED: Indicates FACP disconnect
is triggered.
Individual
Voltage LEDs: Indicate 12VDC (Green) or
24VDC (Red).
Environmental:
Operating temperature: 0ºC to 49ºC ambient.
Humidity: 20 to 85%, non-condensing.
Enclosure Dimensions (approximate H x W x D):
15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm).
Agency Listings:
UL Listed Sub-Assembly for US Installations:
UL 294, 7th Edition** - UL Listed for Access Control System Units.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listed Sub-Assembly for Canadian Installations:
“Signal Equipment” Evaluated to CSA Standard C22.2
No.205-M1983