Data Sheet
AL1012ULXB
Off-line Switching Power Supply/Charger
Rev. DSAL1012ULXB_05052015
Overview
Specifications
AL1012ULXB power supply/charger converts a 115VAC, 60Hz input into a
single 12VDC non-power limited output.
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
0.36”
(9.14mm)
6.7”
(170.18mm)
3.7”
(93.98mm)
4.5”
(114.3mm)
0.185”
(4.7mm)
7.25”
(184.15mm)
Ø
0.156”
(3.96mm)
Agency Approvals
UL Recognized component for Access Control System Units (UL 294).
Board Dimensions (L x W x H approximate):
4.5” x 7.25” x 1.75” (114.3mm x 184.15mm x 44.45mm)
Input:
• Input 115VAC, 60Hz, 2.6 amp.
• Input fuse rated @ 5 amp/250V.
Output:
• 12VDC output.
• 10 amp continuous supply current.
• Output fuse rated @ 15 amp/32V.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• 61.42 BTU/Hr.
• System AC input VA requirement: 299VA.
Mechanical:
• Product weight (approx.): 0.75 lbs. (0.34 kg).
• Shipping weight (approx.): 0.9 lbs. (0.41 kg).
AL1012ULXB