Installation Instructions
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC.Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
Terminal Identification:
Terminal Legend Function/Description
L,G,N Connect115VAC/60Hztotheseterminals:Ltohot,Ntoneutral,Gtoground.
+DC– 12VDC@10ampcontinuousnonpower-limitedoutput.
ACFAIL
NC,C,NO
UsedtonotifylossofACpower,e.g.connecttoaudibledeviceoralarmpanel.Relaynormally
energizedwhenACpowerispresent.Contactrating1amp@28VDC.ACorbrownoutfailis
reportedwithin1minuteofevent.
BATFAIL
NC,C,NO
Usedtoindicatelowbatterycondition,e.g.connecttoalarmpanel.Relaynormallyenergizedwhen
DCpowerispresent.Contactrating1amp@28VDC.Aremovedbatteryisreportedwithin
5minutes.Batteryreconnectionisreportedwithin1minute.
Lowbatterythreshold:@approximately10.5VDC.
+BAT– Stand-bybatteryconnections.Maximumchargecurrent0.7amp.
NC C NO NC C NO
BAT FAIL AC FAIL
AC DELAY
VR1
15
5A 250V
LG N
Fig. 1