Installation Guide
  M220 Series Installation Guide  - 13 -
AL1024M220 Battery Size Calculation Worksheet.
A.  AL1024M220 internal current consumption  (stand-by)     0.13A
B.  Load current consumption  (stand-by)     A
C.  Stand-by time required (hours)       H
D.  Battery capacity required for stand-by  (A+B)*C     AH
E.  AL1024M220 internal power consumption  (Alarm)      0.13A
F.  Load current consumption  (Alarm)     A
G.  Alarm duration  (Alarm)     H
  (Hours, example: 15 Min = 0.25 Hour)
H.  Battery capacity required for Alarm  (E+F)*G     AH0
I.  Total calculated battery capacity  D+H     AH
J.  Battery capacity required  I*1.8 (safety factor)     AH
Note: AL1024M220 power supply is designed to work with batteries up to 65AH. Please note, line [I] must not 
exceeds 36AH. You have to reduce either standby current consumption or standby time in order to comply with 
requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.