Spec Sheet
- Eight (8) independently controlled outputs.
- Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs;
b) Eight (8) form “C” 5A rated relay outputs;
c) Any combination of the above.
- Eight (8) auxiliary power outputs (unswitched).
- Output fuses are rated @ 3.5A.
- Filtered and electronically regulated outputs.
- Supervision:
- AC Fail
- Battery Fail and Battery Presence.
- Fire Alarm disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs.
- Alarm output relay indicates that FACP input is triggered.
- Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input
b) Polarity reversal input from FACP signaling circuit.
- Built-in charger for sealed lead acid or gel type batteries.
- Instantaneous transfer to stand-by batteries.
- CE European Conformity.
- Lifetime Warranty
ACM220 Series Power Supply Configuration Reference Chart
Altronix
Model Number
12VDC Total
Output
Current
24VDC Total
Output
Current
Fused
Outputs
Individual
Output
Rating
220VAC 50/60Hz
Input
Current Draw
Power Supply
Board Input
Fuse Rating
Power Supply
Board Battery
Fuse Rating
AL400ACM220
4A 3A
8 2.5A
1.2A
5A/250V
15A/32V
AL400ACMJ220
AL600ACM220
6A 6A 1.5A ---------
AL600ACMJ220
AL1012ACM220
10A --------- 2.2A
15A/32V
AL1012ACMJ220
AL1024ACM220
--------- 10A 3A 6.3A/250V
AL1024ACMJ220
Key Features
AL600ACM220
Rev. 12132021
ACM220 Series
Power Supply/Chargers with Multi-Output Access Power Controllers
Altronix ACM220 series distribute and switch power to access control systems and acces-
sories. They convert a 220VAC 50/60Hz input into eight (8) independently controlled 12VDC
or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C”
contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger
input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will
route power to a variety of access control hardware devices including: Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-
Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may
be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the eight (8) outputs.
Lifetime Warranty
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com