Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(Stand-by Specifications Chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the bat-
tery terminal and at the board terminals marked [--- B AT + ] to ensure that there is no break in the battery connection wires.
Note:Maximumchargingcurrentunderdischargeis500mA.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.