Installation Instructions Instruction Manual

AL1002ULADAJ - 11 -
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base
Detector Type
Max Stand-by
Current (mA)
Alarm
Current (mA)
SystemSensor4WTR-B(12/24volt)
I
3
Photow/Therm/
Sounder/Relay
0.05 50
SystemSensor4WITAR-B(12/24volt) I
3
Photow/IsolatedTherm/Sounder/Relay 0.05 50
SystemSensor2W-MOD2 I
3
LoopTest/MaintenanceMod. 0.05 *
SystemSensorRRS-MOD I
3
ReversingRelay/SyncModule 0.05 *
SystemSensor6424 ProjectedBeam 10 28.4
SystemSensorBeam1224(S) ProjectedBeam 17 38.5
*Contactmanufacturerforcurrentdraws
A.2 Door Holders
TableA-2belowlistsdoorholderscompatiblewithAL1002ULADAJAUXoutput.
Manufacturer Model Type Current (mA)
Edwards DH150A FloorMount 96
Edwards DH154A FloorMount 96
Edwards DH158A SurfaceMount 96
RixonFiremark FM-980 FloorMount,single 68
RixonFiremark FM-996 SurfaceWiring 68
RixonFiremark FM-998 ConcealedWiring 68
A.3 Relays
TableA-3belowlistsrelayscompatiblewithAL1002ULADAJAUXoutput.
Manufacturer
Model Current (mA)
Manufacturer Model
Current (mA)
AirProducts&
Controls,LTD
MR-101/C
MR-201/C
PAM-1
PAM-2
PAM-SD
A77-716B
15
35
15
15
15
20
SystemSensor
PR-1
PR-2
PR-3
EOLR-1
R-10T
R-14T
R-20T
R-24T
R-10E
R-14E
R-20E
R-24E
15
30
30
30
23
23
40
40
23
23
40
40