AL1002ULADAJ NAC Power Extender Installation Guide (See Application Guide for additional information) Altronix Corp. 140 58th St. Brooklyn, NY Rev.
AL1002ULADAJ - NAC Power Extender Overview: The Altronix AL1002ULADAJ is an extremely cost effective 10 amp remote power supply/battery charger. It may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories.
Power Supply Specifications: AC Input: Output: Battery: 120VAC 60Hz, 5 amp supplied by a maximum 15 amp dedicated branch circuit. Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total output current must not exceed current 10 amp in Alarm Condition. Use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries connected in series.
6. Connect FACP output to the desired AL800LGK logic board inputs, and notification appliances to the desired AL800LGK logic board outputs (see Application Guide). Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability. 7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 7.
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. Amount of Notification Appliances per unit: Amseco 27 per NAC* Faraday 39 per NAC* Gentex® 32 per NAC* *Not to exceed a maximum of 2.5 amp per NAC.
Power Supply Board* Terminal Identification Table: Terminal Legend Function/Description L, N Connect 120VAC to these terminals: L to hot, N to neutral. - DC + 24VDC @ 10 amp in alarm non power-limited output. Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, AC FAIL with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC NO, C, NC occurs terminals marked NO and C are closed, NC and C are open.
NEC Power-Limited Wiring Requirements for AL1002ULADAJ Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Optional hookups: 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 3a, pg. 8) to the common trouble input.
Battery Calculation Worksheet Device For each device use this formula: Number of Current per Device Devices This column x This column = Equals AL1002ULADAJ (Current draw from battery) 1 A AL1002 Current Auxiliary Devices Stand-by: 130mA Alarm: 300mA 130mA 300mA 130mA 300mA Refer to device manual for current ratings. Alarm/Stand-by Alarm/Stand-by Alarm/Stand-by B Stand-by Alarm Current Current Current per number of devices.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL1002ULADAJ AUX output.
A.1 Four (4) Wire Smoke Detectors (cont.) Detector Type Smoke Detector/Base System Sensor 4WTR-B (12/24 volt) System Sensor 4WITAR-B (12/24 volt) System Sensor 2W-MOD2 System Sensor RRS-MOD System Sensor 6424 System Sensor Beam 1224(S) * Contact manufacturer for current draws I3 Photo w/Therm/ Sounder/Relay 3 I Photo w/Isolated Therm/Sounder/Relay I3 Loop Test/Maintenance Mod. I3 Reversing Relay/Sync Module Projected Beam Projected Beam Max Stand-by Current (mA) Alarm Current (mA) 0.05 50 0.05 0.
Enclosure Dimensions (H x W x D approximate): 18” x 14.5” x 4.5” (457.2mm x 368.3mm x 114.3mm) 14.5” (368.3mm) 1.5” (38.1mm) 2.5” (63.5mm) 2.5” (63.5mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.0” (25.4mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.5” (38.1mm) 2.5” (63.5mm) 8.5” (215.9mm) 6.0” (152.4mm) 18.0” (457.2mm) 18.0” (457.2mm) 18.0” (457.2mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.0” (25.4mm) 2.75” (69.85mm) 1.5” (38.1mm) 14.5” (368.3mm) 4.5” (114.