ACM8 & ACM8CB Access Power Controllers Installation Guide Models Include: • ACM8 - Fused Outputs • ACM8E - Fused Outputs • ACM8CBE - PTC Outputs • ACM8CB - PTC Outputs Rev.
Overview: These units convert one (1) 12 to 24 volt AC or DC input into eight (8) independently controlled fused or PTC protected outputs. These power outputs can be converted to dry form “C” contacts (ACM8 & ACM8E only). Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.
Installation Instructions: 1. Mount unit in desired location/enclosure. Carefully review: Typical Application Diagram (pg. 4) Terminal Identification Table (pg. 5) LED Diagnostics (pg. 5) Hook-up Diagrams (pg. 6) 2.
Jumper J3 must be cut (Fig. 3, pg. 6). 6. FACP Dry form “C” output (Fig. 1A, pg. 4): Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output. Typical Application Diagram: Fig. 1 ACCESS CONTROL PANEL Fig. 1A KEYPAD NORMALLY OPEN N.O.
LED Diagnostics: ACM8 & ACM8CB Access Power Controller LED ON OFF LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). Terminal Identification Tables: ACM8 & ACM8CB Access Power Controller Terminal Legend Function/Description - Power + 12VDC or 24VDC input from power supply board.
Hook-up Diagrams: Fig. 2 Optional hook-up using two (2) isolated power supply inputs: Fig. 3 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPER J3 CUT JUMPERS J1 AND J2 J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8 POWER) J1 INTERFACE J3 TRG Fig. 4 Normally Open - Non-Latching FACP trigger input: Fig. 5 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) J3 INTERFACE J3 TRG N.O.
Enclosure Dimensions (ACM8E/ACM8CBE): 15.5”H x 12”W x 4.5”D 1.285 1.
Notes: Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.