User guide
8
A typical plumbing schematic connecting 3 x 1200 boilers together.
NOTE the increase in pipework sizing to ensure proper ow through the boilers.
Ensure there are no restrictions in the heating circuit such as thermostatic radiator valves etc.
Expansion vessel etc. has not been shown on this schematic.
For 2 x 1200 boilers, 28mm pipework ow and return is required.
A bypass must be tted. Preference should be made for a 600 x 600 radiator.
FIGURE FOUR: THREE BOILER PLUMBING SCHEMATIC
AUTOMATIC AIR VENT EXPANSION / SAFETY
RELIEF SYSTEM
SERVICE
VALVE
PUMP
AMPTEC BOILER
FLOW
DRAIN VALVE
AMPTEC BOILER
AMPTEC BOILER
35mm PIPE
FLOW
36 LITRE/
MIN
28mm PIPE
FLOW
24 LITRE/
MIN
22mm PIPE
FLOW
12 LITRE/
MIN
35mm PIPE
FLOW
36 LITRE/
MIN
28mm PIPE
FLOW
24 LITRE/
MIN
22mm PIPE
FLOW
12 LITRE/
MIN
RELAY
SYSTEM
95970136
RETURN