User guide
24
IF THE PUMP NEON ON THE PCB DOES NOT
ILLUMINATE WHEN THE CALL IS ILLUMINATED
REPLACE THE CONTROL PCB.
YES
 IS THE 
 PUMP NEON
ILLUMINATED
CHECK AND OPEN SERVICE VALVES.
CHECK AND REPLACE THE PUMP.
NO
IS THE PUMP
 RUNNING
CHECK FOR A RESTRICTION IN THE FLOW.
CHECK THE BYPASS, CHECK THE SERVICE
AND RADIATOR VALVES.
CHECK FOR AIR IN THE SYSTEM.
NO
YES
 ALARM TRIPS AFTER A
FEW MINUTES OF OPERATION
YES
TRIPPING
 DAILY
CHECK FLOW AND PRESSURE.
CHECK FOR TEMPORARY RESTRICTIONS IN FLOW.
CHECK CONNECTIONS ON THERMOSTATIC SWITCH
CONN3.
CHANGE CONTROL PCB.
NO
OCCASIONAL TRIPPING
CHECK FLOW AND PRESSURE.
CHECK FOR TEMPORARY RESTRICTIONS IN FLOW.
CHECK CONNECTIONS ON THERMOSTATIC SWITCH
CONN3.
RESET.
THERE IS NO WATER IN THE SYSTEM.
SWITCH OFF IMMEDIATELY.
CHECK AND FILL BEFORE RESTARTING.
ALARM TRIPS DURING 
SELF CHECKING BUT NOT
INSTANTLY
FIGURE TWENTY ONE: ALARM THREE
FIGURE TWENTY: ALARM TWO
FIGURE TWENTY TWO: ALARM FOUR