User guide

21
12.0 FAULT FINDING
1 Should the ALARM indicator illuminate ‘ashing’ (red) instantly on power up, then the connections
‘Conn 4’have become loose or disconnected in transit or if the ALARM indicator is ‘ashing’ (red) and
the CALL indicator is (red), then ‘Conn 3’ or the thermostatic switch wires have become loose.
2 Should the ALARM indicator illuminate ‘ashing’ (red) during the call checking period then there is a
problem due to lack of water or air in the system.
3 Should the ALARM indicator illuminate ‘ashing’ (red) and the CALL light show (red) after heat is
applied then there is a problem due to lack of water ow. See Fault Finding chart.
NOTE: It may be necessary to t a capacitor between the ‘R’ run and ‘N’ neutral terminals on the control connector
to prevent the boiler continuing to run when the cylinder and the room thermostats are satised. This is due to
a leakage current from some manufacturers 3 port valves. The capacitor required is 0.47 micro-farads suitable
for 275 volts AC (X2 style). These capacitors are available from Heatrae Sadia 95 612 708.
13.0 ALARM RESET
There are 3 steps to re-set a tripped condition: -
1 Switch “OFF” the electrical supply.
2 Correct the fault, check the system is full of water and set to the correct pressure (sealed systems) and
there is a good ow of water (i.e. all the valves are open).
3 Switch the supply back “ON”.
Ensure the customer fully understands the operation of the system.
The Boiler must NOT be operated if it is known to have a fault. Switch off, and call a service engineer.